Abstract of Compare
Energy & Cost savings of Chilled Beam vs. Variable Air Volume Systems
The
research is about the comparison of energy and cost of chilled beam versus
variable air volume. The cooling load calculations in the energy saving of VAV
are performed. Cost and energy analysis are carried out and it’s evaluated that
system which gives a better saving. The VAV could also save much energy which
is compared by the different types of the HVAC system and demand for more investment.
The water distribution system is known was waterside while airside refers to
the air distribution system. There is the following section which explained the
cost and the energy-saving od Chilled beams and VAV.
Introduction of Compare Energy & Cost savings
of Chilled Beam vs. Variable Air Volume Systems
Variable
Air Volume (VAV) of Compare Energy
& Cost savings of Chilled Beam vs. Variable Air Volume Systems
Variable
Air Volume (VAV) Multiple VAV boxes make up a VAV system that controls the air
supply of an individual zone though modulating a damper dependent on the demand
of the load. Load demand is determined with the help of a thermostat which
triggers the opening or closing of damper and consequently speeding up or
slowing down the fan until the static pressure reaches the set-point. To ensure
that air temperature is maintained at setpoint during a part load condition, the
reheat coil is used. Water reheat and electric reheat are the two kinds of
reheat. Hot water from external sources like boiler etc. is used in water
rehear while electric reheat use a coil to provide direct heat to the supply
air (SCANES, 2016)
Chilled
beam of Compare Energy
& Cost savings of Chilled Beam vs. Variable Air Volume Systems
Designing
efficient water-based systems to provide cooling for a large commercial
building like shopping malls, hospitals, and offices, etc. are very important
as these systems account for more than 40% of total energy consumption in the
buildings. Apart from having high energy expenditure, these systems have very
high operating and maintenance costs. A chilled plant has two parts namely the water
side and the air side. The chilled water distribution system is known was
waterside while the air side refers to the air distribution system. The most
commonly used air distribution systems in practice are Chilled Beam (CB) and
Variable Air Volume (VAV) Chilled beam.
There are two types of
chilled beams which are known
·
Active Chilled Beam (ACB)
·
Passive Chilled Beam (PCB).
In PCB, the heat exchange
between the entering air and coil is achieved using natural means where the
difference of density between cold and warm air causes air movement through the
coil. While in ACB, the air handler is used to supply primary air which induces
the room air to pass through the secondary coil and before entering the room it
mixes with the primary air. ACB has better performance and is also efficient as
compared with PCB due to forced convection (Yau et al , 2018).
Figure:
Passive Chilled Beam and Active Chilled Beam
Analysis of Compare
Energy & Cost savings of Chilled Beam vs. Variable Air Volume Systems
Cost-saving
of Chilled beam and VAV of
Compare Energy & Cost savings of Chilled Beam vs. Variable Air Volume
Systems
VAV
system is a common system that is used in invasive areas of healthcare
facilities. When considering the cost factor for both chilled beam and VAV the
initial cost of the chilled beam is higher as compared to VAV. The main cost
issues are associated with the secondary chilled water pipe, the beam itself,
and the heat exchanger. However, on contrary the operation cost of the chilled
beam is lower and in the case of long-term usage chilled beam is more cost-saving
instead of high-cost VAV. Here, analysis is carried out to demonstrate that the
chilled beam system is potentially better for non-invasive spaces. Chilled
beams indicate more advantages such as low energy consumption, regular
maintenance, improved comfort, and easy commissioning. There is no specified
type of moving parts of chilled beams and it reduces maintenance cost (Yau
& Tam, 2018). Below are some mock
calculations provided to explain the cost of VAVs and chilled beam under
specified conditions of the office rooms.
1. Percent reduction in the primary air is
79%.
2. The average size per room for the
chilled beam is 5 ft.
3. The total estimated cost for the chilled
beam in the typical area is $102, 760 at $4.16/SF.
4. The total estimated cost for VAVs for
the specified area is $15078 at $8.51/SF.
5. The percentage increase in chilled
beams is nearly 700%.
The
add deduct cost analysis define the initial cost impact of using the VAV system
and chilled beam system. the life cycle cost analysis uses the payback period
to determine the cost and savings by using these systems (Yau & Tam, 2018).
Energy-saving
of Chilled beam and VAV
Energy-saving
evaluation of VAV system
The cooling season along
with the heating season is supposed. The energy consumptions of the HVAC system
could also be written as;
By
the different assumptions along with the different operations of the mode of fans
and the terminal equipment’s which leads the difference of round energy
consumption between constant air volume system.
The
energy-saving of a variable air volume system is always compared by the
constant air volume system;
Energy-saving
Chilled beam system of
Compare Energy & Cost savings of Chilled Beam vs. Variable Air Volume
Systems
A
chilled beam is the most important part of the energy-efficient system which is
also required the correct primary air system for the savings of energy. Chilled
beams are also beneficial for the increased volumetric capacity of the heat of
water over air. The water also needs the to the volume which is the same amount for
energy like the air (Tiitus-hvac.blogspot., 2017).
There
are two distinct cooling components of the chilled beam;
·
Induced room air
·
Primary air
According
to researchers the team also determined the various radiations of the chilled
beam system which is also provided for the total energy of saving of 10-21% and
it is also depending on the configuration.
The
energy savings are up to 12% which is used passive chilled beams system and
Midwest condition that is also compared by the traditional system to control
air temperature. The separate chiller by the higher chiller of operating
temperature which could also provide 11% energy savings.
Comparison between VAV chilled beam systems
One
of the majors constitute of reducing global energy consumption and
environmental impact is by reducing consumption of energy at individual levels.
the heat transfer characteristics of both chilled beam and VAV system define
the characteristics of work and estimate the energy performance. the indoor
thermal conditions, configuration, and parallel air volume system are used in
these processes. The results of research conducted by Kim et al. (2019) shows
that usage of the dedicated outdoor air system, a desiccant wheel, and separate
chillers for passive chilled beams induce a significant impact on the relative
energy consumption and energy savings (Kima, Tzempelikos, & Brauna, 2019). The passive chilled
beams provide more efficient outcomes that are 12% for humid and hot climates
and around 20% for the dry and hot climate. The radiative cooling effect
between the passive chilled beams varied between 7% and 8% and it affects the
indoor thermal conditions and energy savings. The energy modeling system
different areas of assessment for the energy savings under climatic zones and
passive chilling. Typical validation shows a free-floating temperature with
external conditions. The results of the research also indicate that the passive
chilled beam system is not capable to provide significant energy savings when
compared to the VAV system. the damper system can reduce the load in the
passive chilled beam system. chilled beam uses low energy consumption and the
reason lies behind the efficient water usage instead of air. Statistics show
that HVAC energy cost is approximately $2.33/SF per annum. The full annual
energy bill is approximately $ 3, 760, 000 (Yau & Tam, 2018).
Conclusion of Compare
Energy & Cost savings of Chilled Beam vs. Variable Air Volume Systems
Summing
up all the discussion it is conduced that the comparison of the energy and cost-saving
of VAV and the chilled beams is presented. The energy evaluation for the variable
air volume is also shown in the calculations form. The cost analysis of VAV and
chilled beams is also performed as shown in the above discussion.
References of Compare
Energy & Cost savings of Chilled Beam vs. Variable Air Volume Systems
Kima, J., Tzempelikos, A., & Brauna, J. E. (2019).
Energy savings potential of passive chilled beams vs air systems in various US
climatic zones with different system configurations. Energy & Buildings,
186(02), 244-260.
Raftery, P. (2017, January 23). Saving energy in variable
air volume systems in existing buildings: minimum airflow rates. Retrieved
from https://www.linkedin.com/pulse/saving-energy-existing-buildings-variable-air-volume-systems-raftery
SCANES, J. (2016, December 12). All-air VAV system versus
chilled-beam-system energy consumption at design and part-load conditions.
Retrieved from https://www.csemag.com/articles/all-air-vav-system-versus-chilled-beam-system-energy-consumption-at-design-and-part-load-conditions/
Titus-hvac.blogspot. (2017, January 31). Chilled Beam
Basics: Energy Savings 101. Retrieved from
http://titus-hvac.blogspot.com/2017/01/chilled-beam-basics-energy-savings-101.html
Yao et al. (2007). Evaluation program for the energy-saving
of variable-air-volume systems. Energy and Buildings, 558–568.
Yau et al. (2018). A COMPARISON STUDY FOR ACTIVE CHILLED BEAM
AND VARIABLE AIR VOLUME SYSTEMS FOR AN OFFICE BUILDING. Energy Procedia,
378–383.
Yau, Y. H., & Tam, J. H. (2018). A COMPARISON STUDY FOR
ACTIVE CHILLED BEAM AND VARIABLE AIR VOLUME SYSTEMS FOR AN OFFICE building. Energy
Procedia, 152(01), 378-383.