Introduction of Network Design and Automation
A
substation will be the combination of controlling, switching as well as voltage
step-down equipment which is also arranged and reduced the sub-transmission
voltage for the primary distribution voltage for the industrial, and commercial
along with the residential loads.
Substations
equipment of Network
Design and Automation
The main equipment in the
Industrial Estate consists of;
Transformer of Network Design and Automation
To
step down the 132Kv primary voltage to the 11Kv suitable for the purpose of
distribution. One the 132Kv/0.415 auxiliary transformer is also required which
supplied the substation by the reliable AC power.
Circuit
breaker of
Network Design and Automation
To
disconnect as well as isolate the faulted section then the circuit breaker is
needed. The Sulphur-hexa-fluoride (SF6) circuit breaker is selected for this
factory design requirement.
Isolating
switches (Isolators)
When
the repair work or the maintenance is carried out it is the main requirement on
the equipment of substation or the feeders, then it to be disconnected form the
supply of the isolator which is normally operated at no load.
The
isolators which are normally interlocked by the circuit breakers as well as the
earthing switches.
Rotating
center post disconnector with grounding switch
Potential
and current transformer
The
voltage as well as current transformer were required which has to step down the
line current from the purpose of the relaying along with the metering.
Busbars of Network Design and Automation
The
outgoing as well as incoming circuit which is connected with the Busbars. Then
the flexible ACSR stranded conductors bus bar is also supported from the two
ends which is the strain insulators selected for the 132Kv Busbars.
Protective
relays of
Network Design and Automation
When
the fault occurs then the protective relays will also operate as well as it
also sends to the trip signal to the circuit breakers. A relays was housed in
the panels of the control room as well as in the Ring Main units.
Lightning
arrestors (Surge Arrestors)
The
lightning arrestors will also protect the equipment of substation from the
switching as well as lighting surges.
Earthing
Switch of Network Design and
Automation
The
earthing which is usually connected among the earth and line conductor as well
as it is also mounted on the isolator frame. It is normally open to the position,
where the line is also disconnected the earth switch and it is closed to discharge
and trapped the charges to earth.
Station
earthing system of Network
Design and Automation
A
station earthing system function is to provide the low resistance path for the
flow of earth with the fault currents as well as also for the protection
devices for proper operation along with the safety equipment as well as
personnel (Electrical-engineering-portal.com, 2019).
Cable
size selection of
Network Design and Automation
The
methods of cable sizing as well as calculation for the electrical cable. The
objective of its report is developing the effective cable sizing model for the
design of substation of factor design on the industrial states. Cable sizing is
very important at the design stage because the cable sizing is to function
endlessly under the full load condition where the exclusive being is damage (Edvard, 2017).
Sizing
cable methods is following the unchanged process;
·
Collect the data about the cables
·
Installation surrounding
·
Load that it will carry
There are basic steps
which determine the cable sizing and the voltage drop as shown in the below figure;
Figure: Determine the cable sizing
Cable
selection sizing formulation of
Network Design and Automation
The
rating of the installed current which is calculated through the multiplying of
base current rating by the every derating factor;
Whereas
is installed rating current
(A), and base current rating,
and product of derating factor.
The
cable requires only to be sized to the cater for the full load current of the
motor;
Full load current, protective device rating, and installed cable current rating
=0.725 otherwise =1. = 0.9. For cables
installed above ground = 1. Ca= Ambient
temperature, = Soil resistivity, =dept of burial, = Thermal Insulation, = the value of current
for ingle circuit at ambient temperature. For cables installed above ground and =1.
For
group of Network Design and
Automation
Cables’
having cross sectional area 16mm 2 or less, design value of mV/A/m is obtained
by multiplying tabulated value by factor given by (Nair et al ,
2016):
Fault
level studies of
Network Design and Automation
The
outdoor open terminal 132Kv switchgear shall not be considered for 132kv/11kv
BSPS either there are new installations for the existing assets which can be
replaced. A cost differential among the outdoor as well as indoor alternative I
now generally open terminal arrangement of outdoor where ether is no longer
offer for the economic solution of life time cost is taken into the account.
For
the given design of factory as shown in the below figure, the outdoor layout
also added the risk failures due to the environmental as well as visual
amenity. Thus the requirements for the land of the factory design on the industrial
estate for the open terminal arrangement is supposed and it greater then the
indoor switchgear which is supposed the bearing cost and the values of land are
not premium.
Figure: Factory design
The
network planning in order to ensure the correct IDMT for the protection system
which is also operating below the reasonable as well as normal abnormal condition
where the network should also be planned as well as arranged.
(Cuddihey, 2017)
Tapings of distribution
transformers
A
tapings which could also be paced either on Low voltage winding and high
voltage windings. Normally a tapping is provided the High voltage winding.
The
fine voltage regulation is also possible by the high voltage winding which is
also carries the large number of turns (Ukpowernetwork, 2012).
A
low voltage winding for the transformer which is also carries the large current.
132kv
Lower voltage transformer
The
winding of transformer is 132kv which should be the star connected by the non-uniform
insulation like the defined IEC 60076. The 11kv and 33kv winding should also
have the uniform insulation like the IEC 60076. On 132/11kV Star/Star Vector
Group Transformers a tertiary winding shall be providing. This shall be rated
at 30% of a transformer rating (Warrington, 2005).
Design
of substation layout
Substation
layout
Design of Network Design
and Automation
The blow design is 132kV/11kV
substation and includes the entire 11kV network up to each factory substation
including the 400V main circuit breaker on the LV side of the transformer.
SCADA
system to monitor and control
SCADA
system is typically control system and in the present analysis it controls and
monitor the network. The process increases money and profitability with the
implementation conditions. The implementation system can be sinkhole of cost
overruns, limited capabilities, and delay. The essentials of SCADA network
technology evaluated parameters measure the best network fit for the system. In
the SCADA networks for the network and delivery to substations, there are two
main elements. The process is required to monitor and control power plant,
water system, delivery of services to the substations, and critical
infrastructure. The network combines intelligent devices with the suitable
interfaces in the system control output and sensors. The SCADA system can be
used to improve the control factor. In the electric power generation,
distribution and transmission, SCADA system is designed to detect the current
flow and line voltage. The process also measures and monitor the operation of
circuit breaker and sections of power grid offline and online. The normal
functionality of SCADA is to control the remote equipment from the operation
centers.
Recommendation
for SCADA functionality
The
SCADA functionality can be used for the improved outcomes with all on-site
equipment and survive under different conditions. The exceptional
functionalities are as follows,
1. Enough
capacity that provide support to the equipment.
2. Rugged
construction with the ability to the withstand and how the services will be
delivered under the extreme conditions of humidity and temperature.
3. SCADA
network is secure and redundant power supply.
Figure 1: A typical
SCADA system
Source:
https://www.researchgate.net/figure/A-typical-SCADA-system_fig1_330133572
Conclusion of Network Design and Automation
Summing
up all the discussion it is concluded that the report is about the design of the
substation 132kv/11 kV for the factor design on industrial estates. All the
requirement and the different points which is mentioned are achieved.